Low-Cost Wireless Structural Health Monitoring of Bridges · Komarizadehasl S, Lozano F, Lozano-Galant JA et al.

5. Conclusions

Developing low-cost sensors is essential for Structural Health Monitoring (SHM) of structures with a low budget for their SHM assessments. These sensors can allow engineers to leave the equipment on the structure for monitoring. In previous works, a Cost Hyper Efficient Arduino Product (CHEAP) was introduced, and its performance was validated in laboratory experiments. This device was a uniaxial accelerometer with a sampling frequency of 85 Hz. The main novelty of CHEAP was to improve the resolution, accuracy, and noise level by using the averaged result of five low-cost digital accelerometers located on the same spot for sampling the same signal from the same direction. However, CHEAP presented a few drawbacks such as a low sampling frequency, not being independent of a computer, being uniaxial, being heavy, having a high Noise Density (ND), not having access to the time of the Internet for future sensor synchronizations, and not being able to be controlled entirely wireless. By upgrading both hardware and software of the CHEAP, a new triaxial Low-cost Adaptable Reliable Accelerometer (LARA) is introduced. The advantages of LARA with respect to CHEAP are:(1)By rewriting codes, LARA achieved a faster sampling frequency;(2)Having a connected Raspberry Pi to the Internet made LARA independent of any attached computer for data sampling;(3)Having aligned correctly, its accelerometers made LARA triaxial;(4)Having a better and more efficient connection reduced LARA’s ND;(5)Having the time of the Internet for future data synchronization;(6)Being completely wireless excluded the need for an engineer’s presence on the site for data acquisition.

To evaluate the LARA performance, resolution, and ND, a set of laboratory experiments was performed. These obtained results show that LARA has less ND ratio than MPU9250 and CHEAP for the same number of acquired data. Furthermore, comparing the effects of MPU9250, CHEAP, and LARA with the reports of the shaking table show that LARA is more accurate in reporting both frequency and acceleration amplitude than MPU9250 and CHEAP in a laboratory experiment with the same time duration.

A field test on a footbridge in Barcelona with a span length of 14 m has been carried out using LARA accelerometer. The generated frequencies of the eigenfrequency analysis from LARA have been validated with a commercial high-precision sensor (HI-INC).